How to prevent the ingress of moisture through the cable of submersible pressure transmitters and level probes?

If you wish to measure the level of a liquid easily and reliably, most people can do this using hydrostatic pressure measurement, e.g. with a submersible pressure transmitter or perhaps a so called level probe. The characteristic submersed application implicates a maximum exposure to the encompassing, mainly water-based medium, respectively to ?moisture?.
Exposure isn’t only limited to the wetted elements of the pressure sensor housing, but additionally to the complete immersed amount of the cable. Furthermore, outside the directly immersed level probe parts, the cable, and specifically the cable end, are often exposed to moisture due to splash water, rain and condensation. This is true not merely during operation, but even more during installation and commissioning, or when maintenance or retrofitting is necessary. Irrespective of the mark application, whether in water and wastewater treatment or in tank monitoring, moisture ingress into the cable ends of the submersible pressure transmitter can occur early and irreversibly with insufficient protection measures, and, in virtually all cases, lead to premature failure of the instrument.
The ingress of moisture into the cable outlet and from there on downwards in to the electronics of the level probe must be actively eliminated by preventive actions by the user. To gauge the level with highest accuracy, the varying ambient pressure above the liquid media, that is also ?resting? on the liquid, must be compensated contrary to the hydrostatic pressure acting on the pressure sensor (see article: hydrostatic level measurement).
Ventilation tube
Thus, it is logical that there surely is a constant risk of a moisture-related failure due to moisture ingress (both via the ventilation tube and through the actual cable itself) if you can find no adequate precautionary measures. To compensate the ambient pressure ?resting? on the media, a ventilation tube runs from the sensor element within the level probe, through the cable and out of the level probe at the end of the cable. Due to capillary action within the ventialation tube useful for ambient pressure compensation, moisture can be transported from the surrounding ambience down to the sensor.
Thus not only air, but also moisture penetrates in to the tube, hence the sensor in the probe and the electronics around it usually is irreparably damaged. This can result in measurement errors and, in the worst case, even to failure of the particular level probe. To avoid any premature failure, the ingress of moisture into the ventilation tube should be completely prevented. Additional protection against moisture penetration through the ventilation tube is provided by fitting an air-permeable, but water-impermeable filter element by the end of the vent tube.
bare wires
Not to be ignored can be the transport of the liquid through high-humidity loads across the only limitedly protected internals of the cable, e.g. across the wires, completely right down to the submersible pressure transmitter. As a leading manufacturer, WIKA uses appropriate structural design to prevent fluid transport, so far as possible, into the electronics of the submersible pressure transmitter. Because of molecular diffusion and capillary effects, a guaranteed one-hundred percent protection on the full lifetime of the submersible pressure transmitter, however, is never achievable.
Hence, it is recommended that the cable is definitely terminated in a waterproof junction box with the correct IP protection (e.g. IP65) which is matched to the installation location. If this cable junction box is exposed to weather and varying temperature conditions, it is also recommended to pay focus on a controlled pressure equalisation as a way to prevent the formation of condensation or perspiration water and pumping effects. To address this technical requirement, as an accessory to a submersible pressure transmitter, you’ll be able to order a link box having an integrated air-permeable, water-impermeable membrane.
Ultimately, moisture ingress can happen not only through the exposed end of the cable, but also through mechanical harm to the cable sheath or as a result of liquid diffusion due to improper chemical resistance of the cable material. In this article ? Buffoon for preventing moisture-related failures of submersible pressure transmitters or level probes? this failure mode is described in detail.
WIKA offers comprehensive solutions for your hydrostatic-pressure level measurement. For further assistance in selecting the submersible pressure transmitter most suitable for the application, please use our contact form.
Please find further information with this topic on our information platform ?Hydrostatic level measurement?